Analog indication type HY-4500S / 5000

Analog indication type HY-4500S / 5000
– Proportional control or ON / OFF control
– Convenient temperature setting
– Secondary output built-in (HY)
– Plug-in method (repair, inspection, exchange convenience)
– Burnout function (output OFF when sensor open circuit)

          

Suffix code

Model Code Description
HY- spuare spuare spuare spuare spuare spuare Analog indication temperature controller
Dimension 4500S 96(W) X 96(H)
5000 72(W) X 72(H)
Control type F ON/OFF control (2 position control)
P Proportional control
Input K K thermocouple
J J thermocouple
R R thermocouple
P RTD Pt100 Ω(IEC)
V 1 – 5 V d.c
C 4 – 20 ㎃ d.c
Control output M Relay
C Current output (4 – 20 mA d.c)
S S.S.R (12 V d.c Voltage pulse output)
Control operation R Reverse action (Heating control)
D Direct action (Cooling control)
Range code Select the standard range code

Specification

[ input ]
Thermocouple K, J, R
RTD Pt100 Ω (100 ℃ at 139.6 Ω)
DC voltage input 1 – 5 V d.c, 4 – 20 ㎃ d.c
Input impedance Thermocouple and DC voltage input (V): approx. 1 MΩ
Allowable signal source resistance Thermocouple (less than 100 Ω). DC voltage (2 KΩ or less)
Allowable wiring resistance Resistance thermometer 10 Ω or less.
(However, the resistance between the three lines should be the same)
Allowable Input Voltage Within ± 10 V (thermocouple, RTD, DC voltage)
Reference contact compensation error ±2.0 ℃ (0 ~ 50 ℃)
[ Performance ]
Indication degree ±2 % of FS ±1 Digit
Insulation Resistance More than 20 MΩ (500 V dc)
Withstand voltage 2,000 V a.c 50/60 Hz for 1 minute (between different live parts)
[ Control functions and outputs ]
Control method Proportional control, ON / OFF control (by type code configuration)
Control operation Reverse operation or forward operation (by type code configuration)
Setting range Same as input range indicator
Proportional band 1 to 10% of F.S (HY-4500 variable) (Model HY-4700, HY-5000 fixed to 3% of FS)
Manual reset ( M  R ) ± 10% of MV
Proportional period About 25 to 30 seconds (relay output), about 2 to 4 seconds (voltage output (SSR))
Hysteresis Approx. 2% of FS, fixed (ON / OFF control)
Input disconnection detection Output when the range is over 10 ℃ OFF
Auxiliary output ( L M ) Model HY-4700 only. Upper / lower limit, upper / lower limit operation
(see model name configuration)
Auxiliary output setting range About 50 ° C (about 400 ° C range)
Auxiliary output hysteresis Fix 1 ℃
● Output
Control output Relay output Contact point: 1c, 250 V a.c 3 A (resistive load)
Voltage output
(SSR)
About 12 V d.c (load resistance 800 Ω or higher)
Current output
(SCR)
4 – 20 ㎃ d.c (load resistance more than 600 Ω)
Auxiliary output (LM) Relay output Model HY-4700 only. Contact point: 1 c, 250 V a.c 3 A (resistive load)
[ General Specifications ]
Power supply voltage 110/220 V a.c, 50/60 ㎐
Voltage variation rate ± 10% of supply voltage
Power Consumption 3 VA max
Ambient temperature 0 – 50 ℃
Ambient humidity 35 to 85% RH (No condensation)
Storage temperature -25 ~ 65 ℃
Vibration (durability) 10 – 55 ㎐, a side amplitude of 0.76 ㎜, three axis directions, 1h
Shock (Durability) 300 m / s², 6 directions, 3 times each
weight HY-5000 : 450 g, HY-4500S : 600 g
[ Range and Input code chart ]
Code No HY-4500S HY-5000
Input Range (℃) Input Range (℃)
1 Pt100 Ω -50 ~ 50 Pt100 Ω -50 ~ 50
3 Pt100 Ω -50 ~ 100 Pt100 Ω -0 ~ 100
5 Pt100 Ω 0 ~ 100 K, Pt100 Ω 0 ~ 200
6 K, Pt100 Ω 0 ~ 300
7 K, J, Pt100 Ω 0 ~ 200 K, Pt100 Ω 0 ~ 400
8 K, Pt100 Ω 0 ~ 300 K 0 ~ 600
9 K, J, Pt100 Ω 0 ~ 400 K 0 ~ 800
10 K 0 ~ 600 K 0 ~ 1200
11 K 0 ~ 800
13 K 0 ~ 1200
14 R 0 ~ 1600