Non-indicating type HY-1000 / 2000 / ND4

Non-indicating type HY-1000 / 2000 / ND4
– Simple temperature set up
– Proportioning control or ON/OFF control
– Burn out (Output OFF when sensor disconnected)
– Plug in type(simple correcting, checking and exchanging)

 Suffix code


[  HY-1000/2000 ]

Model Code Content
HY-1000 spuare spuare spuare spuare spuare spuare 72(W) X 72(H) ㎜
HY-2000 96(W) X 96(H) ㎜
Control type P Proportional control
Input K K thermocouple
P Pt100 Ω
Control output M Relay
Alarm output  N None
Control operation R Reverse action control (for Heating control)
Range code Standard range code number selection

[ ND4 ]

Model Code Content
ND4 spuare spuare spuare spuare spuare spuare 48(W) X 48(H) ㎜  ※ 8-pin socket type
Control type F ON/OFF control (2 position control)
P Proportional control
Input K K thermocouple
P Pt100 Ω
Control output M Relay
Control operation R Reverse action control (for Heating control)
D Direct action control (for Cooling control)
Range code Standard range code number selection
Terminal structure T Terminal type
(Note) Specify the power supply voltage of ND4 separately. 110Va.c. or 220Va.c.

Specification

[ Input ]
thermocouple K
Thermoresistor Pt100 Ω(IEC751)
Input impedance Approx. 1 MΩ(Thermocouple input)
Allowable signal source resistance Max. 100 Ω (thermocouple input)
Allowable wiring resistance Resistance thermometer 10 Ω or less.
(The resistance between the three lines should be the same)
Allowable input voltage Within ± 10 V (thermocouple, RTD, DC voltage)
Reference contact compensation error ±2.0 ℃ (0 ~ 50 ℃)
Control functions and outputs ]
Control Method Time Proportional Control, ON/OFF Control(By type code configuration)
Control operation Reverse action control or Direct action control (By type code configuration)
Setting range Refer to Standard range code
Proportional Band 3 % of Max. Range (fixed)
Proportional Cycle Relay Output : 20 sec
SSR Output : 2 sec (*ND4 only)
Input disconnection detection Output when range is out
Control Output Relay Output : 250Va.c, 3 A (resistive load)
SSR Output : Voltage pulse 12Vd.c. (Resistive Load Min.800 Ω) (*ND4 only)
General Specifications ]
Power supply voltage 110/220Va.c. 60 (110Va.c. or 220Va.c. individual for ND4)
Permissible Voltage
Fluctuation Range
Rated Voltage ±10 %
Consumption Power Max. 3 VA
Insulation Resistance Min.20 MΩ (500Vd.c.)
Dielectric Strength 2000Va.c. 50~60 Hz for 1 minute (Between different live parts)
Ambient Temperature 0 ~ 50 ℃
Ambient Humidity 35 ~ 85% R.H (without condensation)
Storage temperature -25 ~ 65 ℃
Shock Resistance 300 m/s²
Weight HY-1000 : 358g, HY-2000 : 558g, ND4 : 220g
[ Standard Range ]
Code HY-1000 HY-2000 ND4
Input Range (℃) Input Range (℃) Input Range (℃)
1 Pt -50 ~ 50
2 Pt -100 ~ 100
3 Pt 0 ~ 100
5 Pt 0 ~ 200 Pt 0 ~ 200 K, Pt 0 ~ 200
6 K, Pt 0 ~ 300
7 K, Pt 0 ~ 400 K, Pt 0 ~ 400 K, Pt 0 ~ 400
10 K 0 ~ 1200
11 K 0 ~ 1200